InteliLite 9 Global Guide
75
5.4.9 Engine cool down and stop
5.4.16 Additional running engine indications
5.4.17 Voltage phase sequence detection
5.4.18 Gen-set operation states
5.4.21 Alternate configuration
5.4.23 ECU Frequency selection
5.4.1 Start-stop sequence
State
Condition of the transition
Action
Next state
Ready
Start request
on
counter started
Prestart
RPM > 2 or Oil pressure >
or Generator
voltage > 10V or D+ voltage is
higher than
Stop (Stop
fail)
OFF Mode selected or Shutdown
alarm active
Not Ready
Not Ready
RPM < 2, Oil pressure not
detected, Generator voltage < 10V,
D+ not Active no shutdown alarm
active, other than OFF Mode
selected
Ready
Prestart
Prestart time elapsed
on,
on,
counter
started
Cranking
Cranking
RPM > Starting RPM
off,
off
Starting
D+ input activated or oil pressure
detected or Generator voltage >
off,
off
Cranking