InteliLite 9 Global Guide
161
Setpoint group
Engine settings
Related FW
1.1.0
Range [units]
0 .. 600 [s]
Default value
2 s
Alternative config
NO
Step
1 s
Comm object
8394
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Time of closing of the
output prior to the engine start. Set to zero if you want to leave
the output
open.
Image 8.1 Prestart Time
Prestart Time
Setpoint group
Engine settings
Related FW
1.1.0
Range [units]
5 .. 50 [%]
Default value
25%
Alternative config
NO
Step
1 % of
Comm object
8254
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
This setpoint defines the “firing” speed level as percent value of the
. If this level is
exceeded the engine is considered as started.
Starting RPM