InteliLite 9 Global Guide
197
Group: Protections
Subgroup: Overload Protection
Setpoint group
Protections
Related FW
1.1.0
Range [units]
Enabled/Disabled/By LBI [-]
Default value
Enabled
Alternative config
NO
Step
[-]
Comm object
15664
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
This setpoint adjusts the behavior of generator Overload protection.
Enabled:
Protection is enabled. Behavior of protection is adjusted via setpoints
and
.
Disabled:
Protection is disabled.
By LBI:
Protection is enabled or disabled by the state of LBI
.
Overload Protection
Subgroup: Current Protection
Setpoint group
Protections
Related FW
1.1.0
Range [units]
Enabled / Disabled / By LBI [-]
Default value
Enabled
Alternative config
NO
Step
[-]
Comm object
15665
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
This setpoint adjusts the behavior of generator Short Circuit protection.
Enabled:
Protection is enabled. Behavior of protection is adjusted via setpoints
and
Short Circuit BOC Delay (page 193)
.
Disabled:
Protection is disabled.
By LBI:
Protection is enabled or disabled by the state of LBI
.
Short Circuit Protection
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...