Setpoint group
Engine settings
Related FW
1.1.0
Fixed value
5 s
Description
Delay for
Battery Undervoltage (page 188)
and
Battery Overvoltage (page 188)
protection.
IMPORTANT: This is a fixed parameter, it isn't possible to adjust it in any manner. This
parameter isn't visible either in controller or in PC tools.
Battery <> Voltage Delay
Setpoint group
Engine settings
Related FW
1.1.0
Range [units]
Disabled / 1–240 [min]
Default value
Disabled
Alternative config
NO
Step
1 min
Comm object
15766
Related applications
MRS
Config level
Advanced
Setpoint visibility
Always
Description
This setpoint enables battery charging and defines the time gen-set is running for to recharge battery. If
battery charging is enabled and battery undervoltage is detected for more than 5 minutes, gen-set is started
and will run for time defined in setpoint
Low Battery Charging Cycle
.
Battery charging is only initiated in AUT mode when no Shutdown alarm and Fuel Level alarm is active.
If there is battery undervoltage detected again after previous Charging Cycle is finished (and undervoltage
lasts more than 5 minutes) next Charging Cycle is initiated.
If controller is switched to MAN mode during battery charging, gen-set stay running regardless timer (
Low
Battery Charging Cycle
setpoint) elapsing. Gen-set is stopped by STOP button or by any SD alarm event
only in this case.
If there is
Charging Alternator Fail
alarm occurred during battery recharging period, current battery recharging
continues until time is elapsed. Next gen-set start due to battery undervoltage is blocked until controller is
restarted.
IMPORTANT: If controller is in MAN mode and the battery voltage is under the limit more
than 5 minutes engine is started immediately when controller is switched to AUT mode.
Note:
Low Battery Charging function is available only when separate MRS archive is used.
Low Battery Charging Cycle
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...