InteliLite 9 Global Guide
324
Related FW
1.1.0
Related applications
AMF, MRS
Comm object
116
Description
This output is to be used for control of “keyswitch” input of an ECU. If the particular ECU does not have
keyswitch or a similar input, it can be used for control of DC power for the ECU.
The output closes together with
and remains closed for the entire duration that the
engine is running. It is opened at the moment that the engine comes to a stop (i.e. together with the
).
Image 8.24 ECU Power Relay
IMPORTANT: This LBO also affects evaluation of
Sd ECU Communication Fail (page 374)
or
Wrn ECU Communication Fail (page 360)
alarms. With configured LBO ECU Power Relay,
these alarms are evaluated only when this LBO is active. Without configured LBO ECU
Power Relay, these alarm are evaluated all the time.
ECU Power Relay
back to Logical binary outputs alphabetically
Related FW
1.1.0
Related applications
AMF, MRS
Comm object
350
Description
This output is active when the ECU sends an active “red lamp” flag, i.e. it has detected a critical malfunction
and the engine should not be operated until a service check is performed. This flag is taken from the DM1
frame on standard J1939 ECUs. Some ECUs provide this flag in their own proprietary frames and some do
not provide the flag at all.
ECU Red Lamp
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...