InteliLite 9 Global Guide
380
Related applications
AMF, MRS
Description
This alarm evaluates the generator frequency in the phase L1. The following
setpoints are related to it:
Generator Underfrequency BOC (page 196)
Generator <> Frequency Delay (page 196)
back to List of alarms level 2
Alarm Type
Shutdown
Alarmlist message
Sd Oil Pressure
Alarm evaluated
Gen-set is running
Related applications
AMF, MRS
Description
This alarm indicates that the oil pressure is lover than the pressure set in
setpoint.
Sd Oil Pressure
back to List of alarms level 2
Alarm Type
Shutdown
Alarmlist message
Sd Overload
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
The alarm is issued when the gen-set power is over the limit for time period longer
than the delay. The behavior of the overload alarm is adjusted by the following
setpoints:
adjusts the overload limit.
adjusts the delay
Sd Overload
back to List of alarms level 2
Alarm Type
Shutdown
Alarmlist message
Sd Overspeed
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
This alarm occurs immediately when the engine speed has exceeded the limit. The
behavior of the overspeed alarm is adjusted by the following setpoints:
adjust the overspeed limit
adjust the additional overspeed limit
Overspeed Overshot Period (page 179)
adjust the time period of additional
overspeed limit
Sd Overspeed
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...