InteliLite 9 Global Guide
176
Subgroup: Stopping
Setpoint group
Engine settings
Related FW
1.1.0
Range [units]
Idle / Nominal [-]
Default value
Nominal
Alternative config
NO
Step
[-]
Comm object
10046
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Selects the function of the binary output
during engine cooling state.
Idle
Cooling is executed at Idle speed and generator protections are switched off.
Nominal
Cooling is executed at Nominal speed and generator protections are active.
Note:
When ECU is connected the predefined value 900 RPM for Idle speed is requested.
Note:
Binary output
must be configured and connected to speed governor.
Engine Idle speed must be adjusted on speed governor.
Cooling Speed
Subgroup: Stopping Timers
Setpoint group
Engine settings
Related FW
1.1.0
Range [units]
0 .. 3 600 [s]
Default value
30 s
Alternative config
NO
Step
1 s
Comm object
8258
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Runtime of the unloaded gen-set to cool the engine before stop.
Cooling Time
Setpoint group
Engine settings
Related FW
1.1.0
Fixed value
60 s
Description
Under normal conditions the engine must certainly stop within this period after the
has been de-energized and the
energized. The stop solenoid remains
energized for the entire stop time period.
Stop Time
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...