InteliLite 9 Global Guide
256
Setpoint group
Engine settings
Related FW
1.1.0
Range [units]
Primary / Secondary / Default [-]
Default value
Default
Alternative config
NO
Step
[-]
Comm object
15198
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Visible only if ECU is configured
Description
This setpoint is used for choosing a frequency of ECU. Values are saved in ECU.
VOLVO EMS2 (GE engines)
The nominal speed is selected via the VP Status proprietary frame, parameter "Frequency select".
SCANIA EMS/S6
The nominal speed is selected via parameters "Nominal speed switch 1" and "Nominal speed switch 2" in
the DLN1 proprietary frame.
Frequency change for Volvo Penta engines with EMS2
This description refers to the Volvo Penta Application bulletin 30-0-003. The procedure for changing engine
speed on the D9 and D16 engines is different from the D12 engine. There is no system reset on the EMS2
unit; therefore the procedure is changed.
Procedure if ECU not energized:
1. Switch the IL controller to MAN Mode.
2. Power up the ECU.
3. Change the setpoint ECU FreqSelect and confirm it by pressing Enter
4. Press the Stop button on the IL controller.
Note:
The whole procedure (step 2 to 4) must not exceed 10 seconds.
Procedure with ECU powered on:
1. Switch the IL controller to MAN Mode.
2. Press the Stop button on the IL controller.
3. Change the setpoint ECU FreqSelect and confirm it by pressing Enter
4. Press the Stop button on the IL controller.
Note:
The whole procedure (step 2 to 4) must not exceed 10 seconds.
Note:
This value is used when binary input
is active.
ECU Frequency Select 3
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...