InteliLite 9 Global Guide
37
Image 4.19 Wiring of analog input with current sensor
0 - 22 mA
mA
0
1
2
3
4
5
6
7
8
9
10
11
Ω
100
133
167
202
241
283
328
375
431
489
553
625
mA
12
13
14
15
16
17
18
19
20
21
22
Ω
707
793
894
1007
1136
1287
1460
1666
1914
2222
2596
Note:
This is a conversion of current from current sensor to appropriate resistance value. Use resistance
values in InteliConfig to create your specific curve. These values should be used in "Ohm" column.