InteliLite 9 Global Guide
187
Subgroup: Maintenance
Setpoint group
Engine settings
Related FW
1.1.0
Range [units]
-10 000 ... 9 999 [h] / Disabled
Default value
1 000 h
Alternative config
NO
Step
1 h
Comm object
11616
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Maintenance timer 1 counts down when engine is running. If reaches zero, an alarm appears, but the timer
still counting down into negative values. When the value 10000 is set, than the Maintenance function is
disabled and counter does not count. Counter value disappear from controllers statistics.
Maintenance Timer 1
Setpoint group
Engine settings
Related FW
1.1.0
Range [units]
-10 000 ... 9 999 [h] / Disabled
Default value
1 000 h
Alternative config
NO
Step
1 h
Comm object
11617
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Maintenance timer 2 counts down when engine is running. If reaches zero, an alarm appears, but the timer
still counting down into negative values. When the value 10000 is set, than the Maintenance function is
disabled and counter does not count. Counter value disappear from controllers statistics.
Maintenance Timer 2
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...