InteliLite 9 Global Guide
156
Setpoint group
Basic settings
Related FW
1.1.0
Range [units]
Disabled / 1 .. 599 [s]
Default value
10 s
Alternative config
NO
Step
1 s
Comm object
8264
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Setting of horn behavior.
Disabled
Disabling the Horn sounding function
1 .. 599 [s]
Timeout for
binary output. The
output is opened when
this timeout elapsed.
Note:
Horn timeout starts again from the beginning if a new alarm appears before previous Horn timeout
has elapsed.
Horn Timeout
Setpoint group
Basic settings
Related FW
1.1.0
Range [units]
Disabled / 1 - 360 [min]
Default value
Disabled
Alternative config
NO
Step
1 min
Comm object
8548
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Conditioned by the setpoint
Always
Description
The controller is switched to Zero Power Mode when there is no user interaction with the controller for the
preset time period. Zero Power Mode is disabled in AMF automatic mode. For the controller wake up press
button Start
or activate Binary Input 1. The controller will not switch to Zero Power Mode if generator is
running. In Zero Power Mode binary outputs go to high impedance.
Note:
Power consumption of controller in Zero Power Mode is 0 mA. Controller is internally
disconnected from power supply.
Zero Power Mode
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...