InteliLite 9 Global Guide
194
Setpoint group
Generator settings
Related FW
1.1.0
Range [units]
Generator Undervoltage Wrn (page 194)
..
Generator Overvoltage Sd (page 193)
[%]
Default value
110 %
Alternative config
NO
Step
1 % of
Nominal Voltage Ph-N (page 149)
or
Nominal Voltage Ph-Ph (page 149)
Comm object
9686
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold for generator overvoltage protection. All three phases are checked. Maximum out of three is used.
Note:
Phase to phase and phase to neutral voltages are used for this protection.
Generator Overvoltage Wrn
Setpoint group
Generator settings
Related FW
1.1.0
Range [units]
0 ..
Generator Undervoltage Wrn (page 194)
[%]
Default value
70 %
Alternative config
NO
Step
1 % of
Nominal Voltage Ph-N (page 149)
or
Nominal Voltage Ph-Ph (page 149)
Comm object
8293
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold for generator undervoltage protection. All three phases are checked. Minimum out of three is used.
Note:
Phase to phase and phase to neutral voltages are used for this protection.
Note:
When there is no control of breakers, the type of protection is Sd not BOC.
Generator Undervoltage BOC
Setpoint group
Generator settings
Related FW
1.1.0
Range [units]
Generator Undervoltage BOC (page 194)
..
Generator Overvoltage Wrn (page 194)
[%]
Default value
70 %
Alternative config
NO
Step
1 % of
Nominal Voltage Ph-N (page 149)
or
Nominal Voltage Ph-Ph (page 149)
Comm object
9687
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold for generator undervoltage protection. All three phases are checked. Minimum out of three is used.
Note:
Phase to phase and phase to neutral voltages are used for this protection.
Generator Undervoltage Wrn
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...