InteliLite 9 Global Guide
334
LBO: H
Related FW
1.1.0
Related applications
AMF, MRS
Comm object
1373
Description
This output is closed if ECU send signal HEST Lamp. If ECU stop send HEST LAMP signal binary input will
be opened without no matter if alarms in alarmlist are confirmed or not.
HEST Lamp
back to Logical binary outputs alphabetically
Related FW
1.1.0
Related applications
AMF, MRS
Comm object
1
Description
The output designed to be used for acoustic indication of a newly appeared alarm. The output is activated
each time a new alarm has appeared and remains active until one of the following events occurs:
Fault reset
is pressed
Horn reset
is pressed
has elapsed
Horn
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...