Setpoint group
Generator settings
Related FW
1.1.0
Range [units]
0,0 ..
Generator Underfrequency Wrn (page 196)
[%]
Default value
85,0 %
Alternative config
NO
Step
0,1 % of
Comm object
8298
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold for generator phase L1 underfrequency.
Note:
When there is no control of breakers, the type of protection is Sd not BOC.
Generator Underfrequency BOC
Setpoint group
Generator settings
Related FW
1.1.0
Range [units]
Generator Underfrequency BOC (page 196)
..
Generator Overfrequency Wrn (page 195)
[%]
Default value
85,0 %
Alternative config
NO
Step
0,1 % of
Comm object
9689
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold for generator phase L1 underfrequency.
Generator Underfrequency Wrn
Setpoint group
Generator settings
Related FW
1.1.0
Range [units]
0,0 .. 600,0 [s]
Default value
3,0 s
Alternative config
NO
Step
0,1 s
Comm object
8297
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Delay for
Generator Overfrequency BOC (page 195)
Generator Overfrequency Wrn (page 195)
and
Generator Underfrequency BOC (page 196)
protection.
Generator <> Frequency Delay
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...