InteliLite 9 Global Guide
195
Setpoint group
Generator settings
Related FW
1.1.0
Range [units]
0,0 .. 600,0 [s]
Default value
3,0 s
Alternative config
NO
Step
0,1 s
Comm object
9103
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Delay for
Generator Overvoltage Sd (page 193)
Generator Overvoltage Wrn (page 194)
and
Generator Undervoltage Wrn (page 194)
protection.
Generator <> Voltage Delay
Subgroup: Frequency Protection
Setpoint group
Generator settings
Related FW
1.1.0
Range [units]
Generator Overfrequency Wrn (page 195)
.. 200,0 [%]
Default value
110,0 %
Alternative config
NO
Step
0,1 % of
Comm object
8296
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold for generator phase L1 overfrequency.
Note:
When there is no control of breakers, the type of protection is Sd not BOC.
Generator Overfrequency BOC
Setpoint group
Generator settings
Related FW
1.1.0
Range [units]
Generator Underfrequency Wrn (page 196)
..
Generator Overfrequency BOC (page 195)
[%]
Default value
110,0 %
Alternative config
NO
Step
0,1 % of
Comm object
9688
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold for generator phase L1 overfrequency.
Generator Overfrequency Wrn
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...