InteliLite 9 Global Guide
166
Setpoint group
Engine settings
Related FW
1.1.0
Range [units]
-20,0 .. 80,0 [°C]
Default value
0,0 °C
Alternative config
NO
Step
0,1 °C
Comm object
15716
Related applications
MRS. AMF
Config level
Advanced
Setpoint visibility
Only when LBO
is configured and setpoint
= Temp Based.
Description
This setpoint adjust the base temperature for Choke function. When temperature will be higher than this
setpoint, Choke Time will be always 0. When temperature will be lower than this setpoint, Choke Time will
be calculated by curve adjusted via setpoint
. When setpoint
is set to
Fixed Time
value, setpoint
Choke Start Temp
has no effect.