InteliLite 9 Global Guide
154
Setpoint group
Basic settings
Related FW
1.1.0
Range [units]
AMF / MRS [-]
Default value
AMF
Alternative config
NO
Step
[-]
Comm object
12157
Related applications
AMF
Config level
Advanced
Setpoint visibility
Always
Description
Based on this setpoint is defined basic controller function.
AMF
Normal AMF operation
MRS
When MRS mode is selected the controller will not perform AMF functions anymore. MCB
button
will be inactive and also mains measurement and protections will be disabled.
The controller will keep TEST mode and the gen-set in AUTO mode will be able to start by
binary input.
Operation Mode
Setpoint group
Basic settings
Related FW
1.1.0
Range [units]
1 .. 32 [-]
Default value
1
Alternative config
NO
Step
1
Comm object
24537
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Controller identification number. It is possible to set controller address different from the default value (1) so
that more IL controllers can be interconnected (via RS485) and accessed e.g. from MODBUS terminal.
Note:
When opening connection to the controller it's address has to correspond with the setting in PC
tool.
Note:
This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Controller Address
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...