InteliLite 9 Global Guide
175
Setpoint group
Engine settings
Related FW
1.1.0
Range [units]
Minimal Stabilization Time (page 174)
.. 300 [s]
Default value
10 s
Alternative config
NO
Step
1 s
Comm object
8313
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
When the gen-set has been started and the idle timer has elapsed, the generator voltage and frequency must
get within limits within this period of time, otherwise an appropriate shutdown alarm (generator voltage and/or
frequency) is issued.
Image 8.10 Maximal Stabilization Time
Maximal Stabilization Time
Setpoint group
Engine settings
Related FW
1.1.0
Range [units]
0,0 .. 300,0 [s]
Default value
5,0 s
Alternative config
YES
Step
0,1 s
Comm object
10023
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
During the start of the gen-set, some engine protections have to be blocked (e.g. Oil pressure). The
protections are unblocked after the Protect Hold Off. The time starts after reaching Starting RPM.
Protection Hold Off
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...