InteliLite 9 Global Guide
129
2. Write the command argument into the registers 44208-44209 (register addresses 4207-4208). Use function
16.
3. Write the command code into the register 44210 (register address 4209). Use function 6.
4. (Optional) Read the command return value from the registers 44208-44209 (register addresses 4207-4208).
Use function 3.
5. If the command was executed the return value is as listed in the table. If the command was accepted but
there was an error during execution the return value indicates the reason:
a. 0x00000001 – invalid argument
b. 0x00000002 – command refused (e.g. controller not in MAN, breaker can not be closed in the specific
situation etc.)
Action
Command code
Argument
Return value
Engine start *)
0x01
0x01FE0000
0x000001FF
Engine stop *)
0x01
0x02FD0000
0x000002FE
Fault reset *)
0x01
0x08F70000
0x000008F8
Horn reset *)
0x01
0x04FB0000
0x000004FC
GCB toggle *)
0x02
0x11EE0000
0x000011EF
GCB on
0x02
0x11EF0000
0x000011F0
GCB off
0x02
0x11F00000
0x000011F1
MCB toggle *)
0x02
0x12ED0000
0x000012EE
MCB on
0x02
0x12EE0000
0x000012EF
MCB off
0x02
0x12EF0000
0x000012F0
*) This action is an equivalent of pressing the front panel button
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...