InteliLite 9 Global Guide
155
Setpoint group
Basic settings
Related FW
1.1.0
Range [units]
Disabled / Enabled [-]
Default value
Disabled
Alternative config
NO
Step
[-]
Comm object
9983
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
If this function is enabled, the controller will switch automatically to MAN mode when there is a red alarm in
the alarm list and fault reset button is pressed. This is a safety function that prevents the gen-set starting
again automatically in specific cases when fault reset button is pressed.
Example:
Controller is in AUTO mode and there is red inactive unconfirmed alarm and fault reset
button is pressed, controller will start automatically.
Reset To Manual
Setpoint group
Basic settings
Related FW
1.1.0
Range [units]
Disabled / 1 .. 255 [min]
Default value
Disabled
Alternative config
NO
Step
1 min
Comm object
10121
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
The display backlight is switched off when this timer exceed. When setpoint is adjusted to disabled then the
display will be backlighted all the time.
Backlight Timeout
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...