InteliLite 9 Global Guide
172
Subgroup: Starting Timers
Setpoint group
Engine settings
Related FW
1.1.0
Range [units]
0,0 .. 25,0 [s]
Default value
0,5 s
Alternative config
NO
Step
0,1 s
Comm object
10525
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Delay between
and
logical binary inputs.
is closed before
. Lead time is adjusted via this setpoint.
Image 8.6 Fuel Solenoid Lead
Note:
LBO
goes to logical zero when Fuel Solenoid Lead goes to logical one.
Fuel Solenoid Lead
Setpoint group
Engine settings
Related FW
1.1.0
Range [units]
0 .. 600 [s]
Default value
12 s
Alternative config
NO
Step
1 s
Comm object
9097
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Idle Time delay starts when RPM exceeds
. Start fail is detected when during Idle
state RPM decreases below 2 RPM.
The output
remains inactive during the idle period. Binary output Idle/Nominal
opens during Cooling period again. This output can be used for switching the governor between idle and
nominal speed.
Idle Time
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...