Setpoint group
Engine settings
Related FW
1.1.0
Range [units]
0 .. 50 [%]
Default value
20%
Alternative config
NO
Step
1 % of
Comm object
14107
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
This setpoint rise the upper limit of overspeed protection for the time which is defined in setpoint
. In this time the upper limit of protection is
+ Overspeed
Overshoot.
Overspeed Overshot
Setpoint group
Engine settings
Related FW
1.1.0
Range [units]
0 .. 255 [s]
Default value
5 s
Alternative config
NO
Step
1 s
Comm object
14108
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
Description
Time for which is
active. The timer starts in the same time when starter
starts.
Note:
The setpoint is visible only, if
is greater than 0.
Overspeed Overshot Period
Setpoint group
Engine settings
Related FW
1.1.0
Range [units]
the range is defined by analog sensor curve
Default value
the value is defined by
analog sensor curve
Alternative config
NO
Step
the step is defined by analog sensor curve
Comm object
12895
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Visible only if the logical analog input
is configured
Description
Warning or history threshold level for
.
Oil Pressure Wrn
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...