InteliLite 9 Global Guide
150
Setpoint group
Basic settings
Related FW
1.1.0
Range [units]
0,1 .. 500,0 [V/V]
Default value
1,0 V/V
Alternative config
NO
Step
0,1 V/V
Comm object
9580
Related applications
AMF
Config level
Advanced
Setpoint visibility
Conditioned by the setpoint
Description
Mains voltage potential transformers ratio. If no PTs are used, adjust the setpoint to 1.
Vm PT Ratio
Subgroup: Frequency settings
Setpoint group
Basic settings
Related FW
1.1.0
Range [units]
45 .. 65 [Hz]
Default value
50 Hz
Alternative config
YES
Step
1 Hz
Comm object
8278
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Nominal system frequency (usually 50 or 60 Hz).
Note:
To lock this setpoint against editing you also have to lock setpoint
Nominal Frequency 2 (page 244)
and
Nominal Frequency 3 (page 248)
.
Nominal Frequency