InteliLite 9 Global Guide
168
Setpoint group
Engine settings
Related FW
1.1.0
Range [units]
Disabled / 1–100 [%]
Default value
Disabled
Alternative config
NO
Step
1 %
Comm object
15718
Related applications
MRS. AMF
Config level
Advanced
Setpoint visibility
Only when LBO
is configured.
Description
This setpoint adjust threshold level for deactivation of
binary output. When generator
voltage is higher than this level, then logical binary output C
HOKE
is deactivated. In multiphase system it is
sufficient to deactivate C
HOKE
LBO when at least one voltage crosses this threshold. In case setpoint
Choke Voltage
is set to
Disabled
value, no voltage is taken into account and C
HOKE
LBO isn't deactivated
on the voltage basis.
Choke Voltage
Содержание InteliLite 9