Shutdown
Alarm Type
Shutdown
Alarmlist message
Emergency Stop
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
Alarm is activated when binary input
is activated.
The gen-set shuts down in the moment the input is activated and starting is
blocked until the input is deactivated and fault reset is pressed.
Note:
Use red emergency button placed on the switchboard door and connect
it to a binary input of the controller. Then configure the function Emergency
Stop to this binary input. It is recommended to use NC contact of the button.
Note:
The MCB control is not affected by this alarm.
Emergency Stop
back to List of alarms level 2
Alarm Type
Shutdown
Alarmlist message
Sd Battery Flat
Alarm evaluated
During cranking
Related applications
AMF, MRS
Description
This alarm will be issued if the controller was reset during cranking of the gen-set.
If this situation occurs, the controller supposes the starting battery is so exhausted
that its voltage drops so low when starter motor is energized that it causes
controller reset.
Sd Battery Flat
back to List of alarms level 2
Alarm Type
Shutdown
Alarmlist message
Sd Coolant Temp
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
This alarm indicates that the coolant temperature is higher than the temperature set
in
Coolant Temperature Sd (page 182)
setpoint.
Sd Coolant Temp
back to List of alarms level 2
Alarm Type
Shutdown
Alarmlist message
Sd ECU Communication Fail
Alarm evaluated
With configured LBO
- only when this LBO is
active
Without configured LBO
- all the time
Sd ECU Communication Fail
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...