5.4.3 Operating Modes
Selecting the operating mode is done through Left
and Right
buttons on the front panel or by changing the
setpoint (from the front panel or remotely).
Note:
If this setpoint is configured as password-protected, the correct password must be entered prior to
attempting to change the mode.
Note:
The mode cannot be changed if Access Lock input is active.
The following binary inputs can be used to force one respective operating mode independent of the mode
setpoint selection:
If the respective input is active the controller will change the mode to the respective position according to the
active input. If multiple inputs are active, the mode will be changed according to priorities of the inputs. The
priorities match the order in the list above. If all inputs are deactivated, the mode will return to the original
position given by the setpoint.
OFF
No start of the gen-set is possible .Controller stays in Not ready status and cannot be started any way. The
MCB is closed permanently (
= GENRUN) or is open or closed according to whether
the mains is present or not (
= MAINSFAIL). No AMF function will be performed. The
buttons MCB
, GCB
, Start
and Stop
including the appropriate binary inputs for external buttons
are not active.
IMPORTANT: When engine is running, it is not possible to switch gen-set to OFF mode.
MAN
The engine can be started and stopped manually using the Start
and Stop
buttons (or external buttons
wired to the appropriate binary inputs) in MAN mode. When the engine is running, GCB can be closed. Also
MCB can be closed and opened manually using the MCB button, regardless of whether the mains are present or
not. No auto start is performed.
Note:
The controller provides interlock between GCB and MCB, it means it is never possible to close both CB
together.
AUTO
The controller does not respond to buttons Start
, Stop
, MCB ON/OFF
and GCB ON/OFF
. Engine
start/stop request is evaluated form Mains failure/return.
Note:
When the AMF function will start the engine than the engine will be running at least for the time which is
defined in
setpoint, even if the mains would return in the meantime.
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...