InteliLite 9 Global Guide
133
Starting the engine
Before starting engine you may need to write password. Depends on your settings in controller.
Table
Register addresses
Number of registers
Access
Data type
Meaning
4207 - 4208
2
read/write
Unsigned32
Writing:command argument
Reading: command return value
4209
1
write
Unsigned16
Command code
Table
List of commands and arguments (page 128)
Action
Command code
Argument
Return value
Engine start
0x01
0x01FE0000
0x000001FF
Engine stop
0x01
0x02FD0000
0x000002FE
Request 1/2: (Numbers in Hex)
01
10
10
6F
00
03
06
Controller address
Modbus function
10
hex
= 16
dec
Register address
106F
hex
=
4207
dec
Number of registers
Data length in bytes
Request 2/2: (Numbers in Hex)
01
FE
00
00
00
01
68
0B
Argument
Command code
CRC
Note:
Command and argument may be written as one "packet" (function 16) or you can split it and write
argument (function 16) and after that write command code (function 6).
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...