InteliLite 9 Global Guide
128
Register
addresses
Number of
registers
Access
Data type
Meaning
4200 - 4201
2
read/write
Time
RTC Time in BCD code
4202 - 4203
2
read/write
Date
RTC Date in BCD code
4204
1
read/write
Unsigned8
Index of the language that is used for text
data provided by MODBUS (e.g. alarmlist
messages).
4205 - 4206
2
read
Unsigned32
Last application error. To be read after the
device returns the exception code 04. It
contains specific information about the error.
4207 - 4208
2
read/write
Unsigned32
Writing:command argument
Reading: command return value
4209
1
write
Unsigned16
Command code
4010
1
-
-
Not implemented
4211
1
write
Unsigned16
Password
4212 - 4213
2
read
Unsigned32
Communication status
4214
1
read
Unsigned8
Number of items in the Alarmlist
4215 - 4241
27
read
Alarm
1. record in alarm list
4242 - 4268
27
read
Alarm
2. record in alarm list
4269 - 4295
27
read
Alarm
3. record in alarm list
4296 - 4322
27
read
Alarm
4. record in alarm list
4323 - 4349
27
read
Alarm
5. record in alarm list
4350 - 4376
27
read
Alarm
6. record in alarm list
4377 - 4403
27
read
Alarm
7. record in alarm list
4404 - 4430
27
read
Alarm
8. record in alarm list
4431 - 4457
27
read
Alarm
9. record in alarm list
4458 - 4484
27
read
Alarm
10. record in alarm list
4485 - 4511
27
read
Alarm
11. record in alarm list
4512 - 4538
27
read
Alarm
12. record in alarm list
4539 - 4565
27
read
Alarm
13. record in alarm list
4566 - 4592
27
read
Alarm
14. record in alarm list
4593 - 4619
27
read
Alarm
15. record in alarm list
4620 - 4646
27
read
Alarm
16. record in alarm list
List of commands and arguments
"Commands" are used to invoke a specific action in the controller via the communication channel. The list of
available actions is in the table below. The general procedure of writing a command via MODBUS is as follows:
1. (Optional) Write required level of password into the register 44212 (register address 4211). Use function 6. If
the password is required or not depends on configuration of access rules. It can be adjusted/modified by
InteliConfig.
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...