InteliLite 9 Global Guide
34
4.4.8 E-Stop
E stop has dedicated terminal T09. Power supply of binary output 1 and binary output 2 (terminals 4 and 5) is
internally connected (in controller) to E-Stop terminal. It means higher security and faster disconnection of these
outputs. More information about E-Stop functions
Note:
This function has the same behavior as binary input
Image 4.15 E-Stop wiring
Note:
Recommended fusing is 12 A fuse.
Note:
Grey dashed line symbolizes internal connection between E-Stop and binary outputs 1 and 2.
Note:
For proper functionality of E-Stop, the terminal T09 must be always wired. Terminal can be connected to
or to terminal T03 (BATT+)
IMPORTANT: Suppression diodes are not indicated, but required.
4.4.9 Analog inputs
The analog inputs are designed for resistive automotive type sensors like VDO or DATCON. The sensors are
connected either by one wire (the second pole is the sensor body) or by two wires.
In the case of grounded sensors, connect the AI COM terminal to the engine body as near to the sensors as
possible.
In the case of isolated sensors, connect the AI COM terminal to the negative power supply terminal of the
controller as well as one pole of each sensor.
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...