InteliLite 9 Global Guide
203
Setpoint group
AMF settings
Related FW
1.1.0
Range [units]
50 ..
[%]
Default value
60 %
Alternative config
YES
Step
1 % of
Nominal Voltage Ph-Ph (page 149)
Comm object
8307
Related applications
AMF
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
Description
Threshold for mains undervoltage. All three phases are checked. Minimum voltage out of three phases is
used.
Mains Undervoltage
Setpoint group
AMF settings
Related FW
1.1.0
Range [units]
0,0 .. 600,0 [s]
Default value
2,0 s
Alternative config
YES
Step
0,1 s
Comm object
8306
Related applications
AMF
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
Description
Delay for
and
protection.
Mains < > Voltage Delay
Subgroup: AMF Frequency Conditions
Setpoint group
AMF settings
Related FW
1.1.0
Range [units]
Mains Underfrequency (page 204)
.. 150 [%]
Default value
102,0 %
Alternative config
NO
Step
1,0 % of
Comm object
8310
Related applications
AMF
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
Description
Threshold for mains overfrequency.
Mains Overfrequency
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...