InteliLite 9 Global Guide
149
Setpoint group
Basic settings
Related FW
1.1.0
Range [units]
80 .. 20 000 [V]
Default value
231 V
Alternative config
YES
Step
1 V
Comm object
8277
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
.
Description
Nominal voltage (phase to neutral).
Note:
To lock this setpoint against editing you also have to lock setpoint
Nominal Voltage Ph-N 2 (page 244)
and
Nominal Voltage Ph-N 3 (page 248)
.
Nominal Voltage Ph-N
Setpoint group
Basic settings
Related FW
1.1.0
Range [units]
80 .. 40 000 [V]
Default value
400 V
Alternative config
YES
Step
1 V
Comm object
11657
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
.
Description
Nominal system voltage (phase to phase).
Note:
To lock this setpoint against editing you also have to lock setpoint
Nominal Voltage Ph-Ph 2 (page 244)
and
Nominal Voltage Ph-Ph 3 (page 248)
Nominal Voltage Ph-Ph
Setpoint group
Basic settings
Related FW
1.1.0
Range [units]
0,1 .. 500,0 [V/V]
Default value
1,0 V/V
Alternative config
NO
Step
0,1 V/V
Comm object
9579
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Generator voltage potential transformers ratio. If no PTs are used, adjust the setpoint to 1.
PT Ratio
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...