InteliLite 9 Global Guide
147
Setpoint group
Basic settings
Related FW
1.1.0
Range [units]
1 .. 5 000 [A/5A]
Default value
2 000 A/5A
Alternative config
NO
Step
1 A/5A
Comm object
8274
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Gen-set current transformers ratio.
Note:
Generator currents and power measurement is suppressed if current level is below 1% of CT
range.
CT Ratio
Setpoint group
Basic settings
Related FW
1.1.0
Range [units]
Load / Gen-set [-]
Default value
Gen-set
Alternative config
NO
Step
[-]
Comm object
11625
Related applications
AMF
Config level
Advanced
Setpoint visibility
Always
Description
Adjustment of location of current measurement.
Load:
Current CT´s are physically placed on Load (typically between GCB and MCB).
Gen-Set:
Current CT´s are physically placed on GenSet (typically before GCB).
Note:
For more details about this function see chapter
CT Location
Subgroup: Voltage settings
Setpoint group
Basic settings
Related FW
1.1.0
Range [units]
Mono Phase / SplitPhase / 3Ph3Wire / High Leg D / 3Ph4Wire / Autodetect [-]
Default value
3Ph4Wire
Alternative config
YES
Step
[-]
Comm object
11628
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Connection type
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...