InteliLite 9 Global Guide
162
Setpoint group
Engine settings
Related FW
1.1.0
Range [units]
0,0 .. 10,0 [bar]
Default value
4,5 bar
Alternative config
NO
Step
0,1 bar
Comm object
9681
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Oil pressure limit for starting. The controller will stop cranking (
goes OFF) if the oil
pressure rises above this limit.
IMPORTANT: Value from analog input has higher priority than value from ECU.
Starting Oil Pressure
Setpoint group
Engine settings
Related FW
1.1.0
Range [units]
0 ..
[s]
Default value
0 s
Alternative config
NO
Step
1 s
Comm object
14412
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
This setpoint defines the time before starting when logical binary output
will be
close.
Glow Plugs Time
Содержание InteliLite 9