InteliLite 9 Global Guide
332
Related FW
1.1.0
Related applications
AMF, MRS
Comm object
77
Description
This output is active when the generator voltage and frequency is within limits. It is deactivated:
immediately when the voltage/frequency gets out of limits (when GCB is not closed)
or
with an appropriate delay after the voltage/frequency has got out of limits (when GCB is closed)
Generator Healthy
back to Logical binary outputs alphabetically
Related FW
1.1.0
Related applications
AMF, MRS
Comm object
1252
Description
This output is dedicated for diesel engine only. This output will close for exact time pre-set by setpoint
before every starting attempt. The output opens in same time as the
output closes (100 ms after
output opens).
Image 8.35 Glow Plugs
Glow Plugs