Description
This output is closed when DPF lamp from ECU is active.
RegenerationNeeded
back to Logical binary outputs alphabetically
LBO: S
Related FW
1.1.0
Related applications
AMF, MRS
Comm object
24
Description
This output is dedicated for starter motor control. The number of cranking attempts is adjusted by setpoint
in Engine Settings group. Cranking fail pause is adjusted by setpoint
Image 8.50 Starter
The starter output opens when:
the “firing” speed is reached
maximum time of cranking is exceeded
request to stop comes up
D+ value is higher than
Oil pressure value is higher than
Starting Oil Pressure (page 162)
Generator voltage > 25% of
Nominal Voltage Ph-N (page 149)
or
Nominal Voltage Ph-Ph (page 149)
(any phase)
Starter