Range [units]
1 .. 10 [-]
Default value
3
Alternative config
NO
Step
1
Comm object
8255
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Maximal number of cranking attempts.
Cranking Attempts
Setpoint group
Engine settings
Related FW
1.1.0
Fixed value
8 s
Description
Pause between
.
output is active in this pause until
Cranking Fail Pause elapses.
IMPORTANT: This is a fixed parameter, it isn't possible to adjust it in any manner. This
parameter isn't visible either in controller or in PC tools.
Cranking Fail Pause
Setpoint group
Engine settings
Related FW
1.1.0
Range [units]
1 .. 255 [s]
Default value
5 s
Alternative config
NO
Step
1 s
Comm object
8256
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Maximum time limit of cranking time.
IMPORTANT: There is a protection against broken pinion on starter. In case that there are no
RPM after 5 seconds of starting, cranking is interrupted and cranking fail pause follows.
Maximum Cranking Time
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...