Image 4.18 Wiring of analog input with voltage sensor
0 - 10 V
V
0
1
2
3
4
5
6
7
8
9
10
Ω
81
145
219
306
409
539
685
887
1125
1458
1933
0 - 30 V
V
0
2
4
6
8
10
12
14
Ω
95
134
177
223
274
330
395
465
V
16
18
20
22
24
26
28
30
Ω
543
633
735
853
993
1154
1350
1589
0 - 70 V
V
0
2
4
6
8
10
12
14
16
18
20
22
Ω
99
117
137
155
175
196
219
242
266
291
318
346
V
24
26
28
30
32
34
36
38
40
42
44
46
Ω
375
406
439
473
510
549
589
633
679
729
781
838
V
48
50
52
54
56
58
60
62
64
66
68
70
Ω
873
963
1033
1110
1193
1283
1383
1492
1612
1748
1896
2065
Note:
This is a conversion of voltage from voltage sensor to appropriate resistance value. Use resistance
values in InteliConfig to create your specific curve. These values should be used in "Ohm" column.
Current sensors
Sensor’s output
range (mA)
R (Ω)
0-20
100
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...