InteliLite 9 Global Guide
185
Setpoint group
Engine settings
Related FW
1.1.0
Range [units]
0 .. 900 [s]
Default value
10 s
Alternative config
NO
Step
1 s
Comm object
14343
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Visible only if the logical analog input
is configured
Description
Delay for
.
Fuel Level Delay
Setpoint group
Engine settings
Related FW
1.1.0
Range [units]
the range is defined by ECU sensor curve
Default value
the value is defined by
ECU sensor curve
Alternative config
NO
Step
the step is defined by ECU sensor curve
Comm object
14432
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Visible only if ECU is configured
Description
Warning threshold level for Fuel level which is send from ECU.
ECU Fuel Level Wrn
Setpoint group
Engine settings
Related FW
1.1.0
Range [units]
the range is defined by ECU sensor curve
Default value
the value is defined by
ECU sensor curve
Alternative config
NO
Step
the step is defined by ECU sensor curve
Comm object
14431
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Visible only if ECU is configured
Description
Shutdown or BOC threshold level for Fuel level which is send from ECU.
ECU Fuel Level Sd
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...