InteliLite 9 Global Guide
305
LBI: E
Related FW
1.1.0
Related applications
AMF, MRS
Comm object
40
Description
The shutdown procedure will start immediately when this input is activated. Input is inverted (NC = normaly
closed) in default configuration.
Note:
In case of controller hardware or software fail, safe stop of the engine doesn’t have to be ensured.
To back-up the Emergency Stop function it is recommended to connect separate circuit for
disconnection of Fuel Solenoid and Starter signals.
For more detail see chapter recommended wiring.
Emergency Stop
back to Logical binary inputs alphabetically
LBI: F
Related FW
1.1.0
Related applications
AMF, MRS
Comm object
191
Description
Binary input has the same function as Fault Reset button
on the InteliLite 9 front panel.
Fault Reset Button
back to Logical binary inputs alphabetically
Related FW
1.1.0
Related applications
AMF, MRS
Comm object
680
Description
When this binary input is activated, the controller send request for force regeneration of DPF (diesel
particulate filter) to ECU.
Note:
ECU with Tier IV support is required for proper functionality.
Force Regeneration
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...