InteliLite 9 Global Guide
335
LBO: I
Related FW
1.1.0
Related applications
AMF, MRS
Comm object
39
Description
This output is used for switching between idle speed and nominal speed of the engine during the startup
phase, if this feature (input) is available on the particular engine. In the case of some EFI engines, the
idle/nominal switching is performed over the communication bus.
The output Idle/Nominal closes after the timer
elapses. The
starts
to countdown when
reached. The underspeed protection is not evaluated during
fixed 5 seconds period after reaching
. A Start Fail protection occurs if the RPM drop
below 2RPM during idle.
Image 8.38 Idle/Nominal
Note:
Connect binary output Idle/Nominal to speed governor to switch the speed:
opened = Idle
closed = Nominal
(for normally open contact type)
Idle/Nominal
back to Logical binary outputs alphabetically
LBO: M
Related FW
1.1.0
Related applications
AMF
Comm object
78
Description
This output is active while mains failure is not detected and mains voltage and frequency is within limits.
Mains Healthy
back to Logical binary outputs alphabetically
Related FW
1.1.0
Related applications
AMF
MCB Close/Open
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...