InteliLite 9 Global Guide
312
Related FW
1.1.0
Related applications
AMF, MRS
Comm object
38
Description
Use this input to start and stop the gen-set in AUTO mode.
Note:
If the binary input Remote Start/Stop is active and engine is running and mains failure occurs, the
MCB breaker opens, after
the GCB breaker is closed. Once the mains is OK,
the
elapses and the GCB breaker is opened. Then after
is MCB breaker closed. Gen-set remains running as long as binary input Rem Start/Stop is
active. For more details see timing diagram below.
Image 8.22 Remote Start/Stop
Remote Start/Stop
back to Logical binary inputs alphabetically
Related FW
1.1.0
Related applications
AMF
Comm object
61
Description
When input is closed, the controller automatically transfers load from the mains to the gen-set. Load is
automatically transferred back to the mains when any gen-set shut down protection activates.
Rem TEST On Load