InteliLite 9 Global Guide
360
Alarm Type
Warning
Alarmlist message
Wrn Coolant Temperature Low
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
This alarm indicates that the coolant temperature is lower than the temperature set
in
Coolant Temperature Low Wrn (page 183)
setpoint.
Wrn Coolant Temperature Low
back to List of alarms level 1
Alarm Type
Warning
Alarmlist message
Wrn Coolant Temp
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
This alarm indicates that the coolant temperature is higher than the temperature set
in
Coolant Temperature Wrn (page 181)
setpoint.
Wrn Coolant Temp
back to List of alarms level 1
Alarm Type
Warning
Alarmlist message
Wrn ECU Communication Fail
Alarm evaluated
With configured LBO
- only when this LBO is
active
Without configured LBO
- all the time
Related applications
AMF, MRS
Description
This alarm occurs when an ECU is configured, but the communication with the
ECU is not established or has dropped out.
Wrn ECU Communication Fail
back to List of alarms level 1
Alarm Type
Warning
Alarmlist message
Wrn Fuel Level
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
This alarm indicates that the fuel level is lower than the level set in
setpoint.
Wrn Fuel Level
back to List of alarms level 1
Alarm Type
Warning
Alarmlist message
Wrn + Name of analog input
Alarm evaluated
All the time
Wrn AIN Prot
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...