InteliLite 9 Global Guide
184
Setpoint group
Engine settings
Related FW
1.1.0
Range [units]
0 .. 900 [s]
Default value
5 s
Alternative config
YES
Step
1 s
Comm object
10270
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Visible only if the logical analog input
is configured
Description
Delay for
Coolant Temperature Low Wrn (page 183)
.
Coolant Temperature Low Delay
Setpoint group
Engine settings
Related FW
1.1.0
Range [units]
the range is defined by analog sensor curve
Default value
the value is defined by
analog sensor curve
Alternative config
NO
Step
the step is defined by analog sensor curve
Comm object
12897
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Visible only if the logical analog input
is configured
Description
Warning or history threshold level for
Fuel Level Wrn
Setpoint group
Engine settings
Related FW
1.1.0
Range [units]
the range is defined by analog sensor curve
Default value
the value is defined by
analog sensor curve
Alternative config
NO
Step
the step is defined by analog sensor curve
Comm object
12898
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Visible only if the logical analog input
is configured
Description
Shutdown or BOC threshold level for
Fuel Level Sd
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...