5.4.5 Stabilization
When the
sequence is finished, the gen-set goes into the stabilization phase. There are
two timers (setpoints) in this phase:
Minimal Stabilization Time (page 174)
starts to count down just after the idle period has finished. Generator
voltage and frequency are not checked (respective protections are not evaluated) and the GCB cannot be
closed even if the generator voltage and frequency are within limits.
Maximal Stabilization Time (page 175)
starts to count down just after the idle period has finished. Generator
voltage and frequency are not checked (respective protections are not evaluated) but, opposite to the
previous timer, the GCB can be closed if generator voltage and frequency are within limits.
In situations where the GCB is closed automatically (AUTO, TEST modes), the closing of GCB will occur in the
first moment when the generator voltage and frequency will get into limits and the
has already elapsed.
In the event that the generator voltage or frequency are not within limits within the
period, the appropriate protection(s) will be activated and the gen-set will be cooled down and
stopped.
Note:
The limits for the generator voltage and frequency are given by setpoints in the
.
Note:
The value of the
Minimal Stabilization Time (page 174)
setpoint has to be lower than the value of
setpoint.
5.4.6 Connecting to load
When the
phase is finished, the gen-set can be connected to the load.
The command for connecting the gen-set to the load is issued either automatically (AUTO, TEST modes) or
manually by pressing the GCB button. The following conditions must be valid:
The gen-set is running and the
Minimal Stabilization Time (page 174)
timer has elapsed.
The gen-set voltage and frequency are within limits.
5.4.7 MRS operation
The "MRS function" represents manual or remote start of gen-set. It is ideal for prime power applications.
The MRS procedure
When the start command is detected, the following steps are performed:
The gen-set is started.
GCB is closed and the gen-set begins to supply the load (in AUTO mode, otherwise GCB button has to be
pressed)
When the stop command is detected, the following steps are performed:
GCB is opened and the gen-set stops supply the load.
After GCB is opened, the gen-set cools down and a stop.
5.4.8 AMF operation
The “AMF function” represents the automatic start in the event that the mains have failed and stop after the
mains have been restored. The automatic start can be enabled or disabled by binary inputs
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...