M17048-245 v4
C
A
B
BC
ANSI05000224-2-en.vsd
ANSI05000224 V2 EN-US
Figure 131:
Example of tapped line with Auto transformer
This application gives rise to similar problem that was highlighted in section
, that is increased measured impedance due to fault current
infeed. For example, for faults between the T point and B station the measured
impedance at A and C will be
Z
A
=Z
AT
+ ·Z
TF
I
A
+ I
C
I
A
DOCUMENT11524-IMG3509 V3 EN-US
(Equation 132)
A
C
2
C
Trf
CT
TB
C
I
I
V2
Z
Z
(Z
Z ) (
)
V1
I
+
=
+
+
×
×
EQUATION1714 V1 EN-US
(Equation 133)
1MRK 504 163-UUS A
Section 8
Impedance protection
Transformer protection RET670 2.2 ANSI
273
Application manual