![ABB RELION RET670 Скачать руководство пользователя страница 147](http://html.mh-extra.com/html/abb/relion-ret670/relion-ret670_applications-manual_4714147.webp)
limit the operation is restrained. It is recommended to use
I5/I1Ratio
=
25%
as default
value in case no special reasons exist to choose another setting.
Transformers likely to be exposed to overvoltage or underfrequency conditions (that is,
generator step-up transformers in power stations) should be provided with a dedicated
overexcitation protection based on V/Hz to achieve a trip before the core thermal limit
is reached.
7.1.3.5
Cross-blocking between phases
M15266-317 v7
Basic definition of the cross-blocking is that one of the three phases can block
operation (that is, tripping) of the other two phases due to the harmonic pollution of the
differential current in that phase (waveform, 2nd or 5th harmonic content). In the
algorithm the user can control the cross-blocking between the phases via the setting
parameter
CrossBlockEn
. When parameter
CrossBlockEn
is set to
Enabled
, cross
blocking between phases will be introduced. There are no time related settings
involved, but the phase with the operating point above the set bias characteristic will be
able to cross-block the other two phases if it is self-blocked by any of the previously
explained restrained criteria. As soon as the operating point for this phase is below the
set bias characteristic cross blocking from that phase will be inhibited. In this way
cross-blocking of the temporary nature is achieved. It should be noted that this is the
default (recommended) setting value for this parameter. When parameter
CrossBlockEn
is set to
Disabled
, any cross blocking between phases will be disabled.
7.1.3.6
External/Internal fault discriminator
M15266-269 v10
The external/internal fault discriminator operation is based on the relative position of
the two phasors (in case of a two-winding transformer) representing the W1 and W2
negative sequence current contributions, defined by matrix expression see the technical
reference manual. It practically performs a directional comparison between these two
phasors.
In order to perform a directional comparison of the two phasors their magnitudes must
be high enough so that one can be sure that they are due to a fault. On the other hand,
in order to guarantee a good sensitivity of the internal/external fault discriminator, the
value of this minimum limit must not be too high. Therefore this limit value
(
IMinNegSeq
) is settable in the range from 1% to 20% of the differential protections
IBasecurrent, which is in our case the power transformer HV side rated current. The
default value is 4%. Only if the magnitude of both negative sequence current
contributions are above the set limit, the relative position between these two phasors is
checked. If either of the negative sequence current contributions, which should be
compared, is too small (less than the set value for
IMinNegSeq
), no directional
comparison is made in order to avoid the possibility to produce a wrong decision.
1MRK 504 163-UUS A
Section 7
Differential protection
Transformer protection RET670 2.2 ANSI
141
Application manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 64: ...58 ...
Страница 74: ...68 ...
Страница 104: ...98 ...
Страница 194: ...188 ...
Страница 518: ...512 ...
Страница 618: ...612 ...
Страница 648: ...642 ...
Страница 666: ...660 ...
Страница 672: ...666 ...
Страница 682: ...676 ...
Страница 844: ...838 ...
Страница 868: ...862 ...
Страница 956: ...950 ...
Страница 964: ...958 ...
Страница 1004: ...998 ...
Страница 1014: ...1008 ...
Страница 1015: ...1009 ...