![ABB RELION RET670 Скачать руководство пользователя страница 485](http://html.mh-extra.com/html/abb/relion-ret670/relion-ret670_applications-manual_4714485.webp)
2
20
0.15
0.3
200
T
ZC
jX
j
j
ohm
=
=
×
=
EQUATION1974 V1 EN-US
(Equation 408)
This corresponds to:
0.3
0.15
0.15 90
2.0
j
ZC
j
pu
pu
=
=
=
Ð
o
EQUATION1975 V2 EN-US
(Equation 409)
Set ZC to 0.15 and
AnglePhi
to 90°.
The warning angle (
StartAngle
) should be chosen not to cross into normal operating
area. The maximum line power is assumed to be 200 MVA. This corresponds to
apparent impedance:
2
2
20
2
200
U
Z
ohm
S
=
=
=
EQUATION1976 V1 EN-US
(Equation 410)
Simplified, the example can be shown as a triangle, see figure
1MRK 504 163-UUS A
Section 8
Impedance protection
Transformer protection RET670 2.2 ANSI
479
Application manual