1.
SendDataUDP[x]
– Enable / disable UDP data stream
2.
ProtocolOnUDP[x]
– Send IEEE1344 or C37.118 on UDP
3.
PMUReportUDP[x]
– Instance number of PMUREPORT function block that must
send data on this UDP stream (UDP client group[x])
4.
UDPDestAddres[x]
– UDP destination address for UDP client group[x] (unicast /
multicast address range)
5.
UDPDestPort[x]
– UDP destination port number for UDP client group[x]
6.
TCPportUDPdataCtrl[x]
– TCP port to control of data sent over UDP client
group[x], i.e. to receive commands and send configuration frames
7.
SendCfgOnUDP[x]
– Send configuration frame 2 (CFG-2) on UDP for client
group[x]
It is possible to turn off/on the UDP data communication either by setting the
parameter
SendDataUDP[x]
to
Disable/Enable
locally in the PMU or by sending a
C37.118 or IEEE1344 command frame (
RTDOFF/RTDON
) remotely from the client to
the PMU as defined in IEEE 1344/C37.118 standard.
However, such a remote control to stop the streams from the client is only possible
when the parameter
SendDataUDP[x]
is set to
SetByProtocol
. The command
RTDOFF/RTDON
sent by the client is stored in the IED, i.e. if the IED is rebooted for
some reason, the state of the stream will remain the same.
If the parameter
SendDataUDP[x]
is set to
Enable
the
RTDOFF/RTDON
commands
received from the clients are ignored in the IED.
It is recommended not to set the parameter
SendDataUDP[x]
to
SetByProtocol
in case
of a multicast. This is because if one of the clients sends the
RTDOFF
command, all
the clients will stop receiving the frames.
The UDP implementation in the IED is a UDP_TCP. This means that by default, only
the data frames are sent out on UDP stream and the header frame, configuration frame
and command frame are sent over TCP. This makes the communication more reliable
especially since commands are sent over TCP which performs request/
acknowledgment exchange to ensure that no data (command in this case) is lost.
However, by setting the parameter
SendCfgOnUDP[x]
to
Enable
, the configuration
frame 2 (CFG-2) of IEEEC37.118 data stream is cyclically sent on the corresponding
UDP stream (UDP client group[x]) once per minute. This is useful in case of multicast
UDP data stream when a lot of PMU clients are receiving the same UDP stream from
the same UDP group (UDP client group[x]).
As shown in Figure
, there are maximum 2 instances of PMUREPORT function
blocks available in the IED. Each UDP client group[x] can only connect to one of the
PMUREPORT instances at the same time. This is defined in the PMU by the parameter
PMUReportUDP[x]
which is used to define the instance number of PMUREPORT
function block that must send data on this UDP stream (UDP client group[x]).
Section 6
1MRK 504 163-UUS A
Wide area measurement system
112
Transformer protection RET670 2.2 ANSI
Application manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 64: ...58 ...
Страница 74: ...68 ...
Страница 104: ...98 ...
Страница 194: ...188 ...
Страница 518: ...512 ...
Страница 618: ...612 ...
Страница 648: ...642 ...
Страница 666: ...660 ...
Страница 672: ...666 ...
Страница 682: ...676 ...
Страница 844: ...838 ...
Страница 868: ...862 ...
Страница 956: ...950 ...
Страница 964: ...958 ...
Страница 1004: ...998 ...
Страница 1014: ...1008 ...
Страница 1015: ...1009 ...