The function shall not operate for any of the calculated currents to the protection. The
minimum theoretical current setting (Imin) will be:
Im
,
fA
fB
in
MAX I
I
EQUATION284 V2 EN-US
(Equation 427)
A safety margin of 5% for the maximum static inaccuracy and a safety margin of 5%
for maximum possible transient overreach have to be introduced. An additional 20% is
suggested due to inaccuracy of instrument transformers under transient conditions and
inaccuracy in the system data.
The minimum primary current setting (Is) is:
I
s
= 1.3 ×
I
min
EQUATION285 V3 EN-US
(Equation 428)
In case of parallel lines with zero sequence mutual coupling a fault on the parallel line,
as shown in Figure
, should be calculated.
~
~
Z
A
Z
B
Z
L1
A
B
I
M
Fault
IED
Z
L2
M
C
Line 1
Line 2
ANSI09000025_2_en.vsd
ANSI09000025 V2 EN-US
Figure 267:
Two parallel lines. Influence from parallel line to the through fault
current: I
M
The minimum theoretical current setting (Imin) will in this case be:
I m in
M A X I
fA
I
fB
I
M
,
,
(
)
³
EQUATION287 V1 EN-US
(Equation 429)
Where:
I
fA
and I
fB
have been described for the single line case.
1MRK 504 163-UUS A
Section 9
Current protection
Transformer protection RET670 2.2 ANSI
533
Application manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 64: ...58 ...
Страница 74: ...68 ...
Страница 104: ...98 ...
Страница 194: ...188 ...
Страница 518: ...512 ...
Страница 618: ...612 ...
Страница 648: ...642 ...
Страница 666: ...660 ...
Страница 672: ...666 ...
Страница 682: ...676 ...
Страница 844: ...838 ...
Страница 868: ...862 ...
Страница 956: ...950 ...
Страница 964: ...958 ...
Страница 1004: ...998 ...
Страница 1014: ...1008 ...
Страница 1015: ...1009 ...