For the
TripAngle
it is recommended to set this parameter to 90° to assure limited
stress for the circuit breaker.
In a power system it is desirable to split the system into predefined parts in case of pole
slip. The protection is therefore situated at lines where this predefined split shall take
place.
Normally the
N1Limit
is set to 1 so that the line will be tripped at the first pole slip.
If the line shall be tripped at all pole slip situations also the parameter
N2Limit
is set to
1. In other cases a larger number is recommended.
8.16.3.2
Setting example for generator application
SEMOD172162-90 v4
In case of out of step conditions this shall be checked if the pole slip centre is inside the
generator (zone 1) or if it is situated in the network (zone 2).
ZC
ZA
ZB
en07000017.vsd
IEC07000017 V1 EN-US
Figure 240:
Generator application of pole slip protection
If the apparent impedance crosses the impedance line ZB – ZA this is the detected
criterion of out of step conditions, see figure
.
Section 8
1MRK 504 163-UUS A
Impedance protection
476
Transformer protection RET670 2.2 ANSI
Application manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 64: ...58 ...
Страница 74: ...68 ...
Страница 104: ...98 ...
Страница 194: ...188 ...
Страница 518: ...512 ...
Страница 618: ...612 ...
Страница 648: ...642 ...
Страница 666: ...660 ...
Страница 672: ...666 ...
Страница 682: ...676 ...
Страница 844: ...838 ...
Страница 868: ...862 ...
Страница 956: ...950 ...
Страница 964: ...958 ...
Страница 1004: ...998 ...
Страница 1014: ...1008 ...
Страница 1015: ...1009 ...